| Electrical Specifications |
| Current measurement DC and AC 10 Hz to 100 Hz |
Range |
40 A / 400 A / 2000 A / 1400 AC rms |
| Resolution |
10 mA / 100 mA / 1 A |
| Accuracy |
A: 1.5% rdg + 15 digits
A: 1.5% rdg + 5 digits |
| Trigger level for Inrush |
0.50 A / 5.0 A / 5 A |
| Trigger level for Hz filter OFF |
2.50 A / 2.5 A / 8 A |
| Trigger level for Hz filter ON |
0.50 A / 2.5 A / 8 A |
| Crest Factor (50/60 Hz) |
Range |
40 A / 400 A / 2000 A / 1400 AC rms |
| Crest Factor1 |
2 @ 33 A, 2.4 @ 27 A
2 @ 330 A, 2.4 @ 270 A
2 @ 1000 A, 2.4 @ 833 A |
| Current measurement AC 100.1 Hz to 1 kHz |
Range |
40 A / 400 A / 2000 A; 1400 AC rms |
| Resolution |
10 mA / 100 mA / 1 A |
| Accuracy |
10 A: 3.5% rdg + 15 digits
10 A: 3.5% rdg + 5 digits |
| Trigger level for Inrush |
0.50 A / 5.0 A / 5 A |
| Trigger level for Hz filter OFF |
2.50 A / 2.5 A / 8 A |
| Trigger level for Hz filter ON |
0.50 A / 2.5 A / 8 A |
Voltage measurement DC and AC 10 Hz to 100 Hz
(600 V and 1000 V ranges have 10% over range to 660 V and 1100 V respectively.) |
Range |
4 V / 40 V / 400 V / 600 V AC rms / 1000 VDC |
| Resolution |
1 mV / 10 mV / 100 mV / 1 V |
| Accuracy |
1% rdg + 10 digits
1% rdg + 5 digits |
| Trigger level for Hz filter OFF |
0.25 V / 6 V |
| Trigger level for Hz filter ON |
0.25 V / 6 V |
Voltage measurement AC 100.1 Hz to 1 kHz
(600 V and 1000 V ranges have 10% over range to 660 V and 1100 V respectively.) |
Range |
4 V / 40 V / 400 V / 600 V ac rms |
| Resolution |
1 mV / 10 mV / 100 mV / 1 V |
| Accuracy |
3% rdg + 10 digits
3% rdg + 5 digits |
| Trigger level for Hz filter OFF |
0.050 V / 0.25 V / 6 V |
| Trigger level for Hz filter ON |
0.050 V / 0.25 V / 6 V |
| Ohms measurement |
Range |
4 kΩ / 40 kΩ / 400 kΩ |
| Resolution |
0.1 Ω / 1 Ω / 10 Ω / 100 Ω |
| Accuracy |
1.5% + 5 digits |
| Continuity beeper |
On at ≤ 30 Ω
Off at ≥ 100 Ω |
| Frequency measurement |
Measurement range |
5.0 Hz to 1 kHz |
| Resolution |
0.1 Hz (15 Hz to 399.9 Hz); 1 Hz (400 Hz to 1 kHz) |
| Accuracy – 5.0 Hz to 100 Hz |
0.2% + 2 counts |
| Accuracy – 100.1 Hz to 1 kHz |
0.5% + 5 counts |
| Trigger level |
Refer to current and voltage tables |
| 1. Add 2% to error spec for CF > 2 |
| General Specifications |
| Batteries |
Six 1.5 V AA NEDA 15 A or IEC LR6 |
| Battery life (with typical usage, backlight off) |
100 hours |
| Test leads |
Rated to 1000 V |
| Weight |
.814 kg (1.8 lb) |
| Jaw size |
58 mm (2.28 in) |
| Dimensions (L x W x D) |
300 x 98 x 52 mm (12 x 3.75 x 2 in) |
| Safety rating |
IEC 61010-2-032, 600 V CAT IV, 1000 V CAT III |
| Environmental Specifications |
| Operating temperature |
32°F to +122°F (0°C to +50°C) |
| Storage temperature |
-4°F to 140°F (-20°C to +60°C) |
| Operating humidity |
0 to 95% (non-condensing) |
| Operating altitude |
2000 m |
| Storage altitude |
10,000 m |
| IP rating |
42 (indoor use only) |
| Drop test requirements |
1 m |
| EMI, RFI, EMC |
FCC part 15, IEC/EN 61326-1:1997 class B
IEC/EN 61326:1997 3 V/m, performance criteria B, EN61325 |
| Temperature coefficients |
Current |
0.1% of reading per °C outside 22°C to 24°C |
| Voltage |
0.1% of reading per °C outside 22°C to 24°C |